0.6/1kV AL/PVC/PVC(or PE) Power Cable
Description
Type |
Description |
No. of cores |
Nominal cross section of conductor |
VLV |
Aluminium conductor/PVC insulation/PVC outer sheath Power Cable |
1, 2, 3, 4, 3+1, 5, 4+1, 3+2 |
1.5~800mm2 |
VLY |
Aluminium conductor/PVC insulation/PE outer sheath Power Cable |
1, 2, 3, 4, 3+1, 5, 4+1, 3+2 |
1.5~800mm2 |
ZA-VLV ZB-VLV ZC-VLV |
Aluminium conductor/PVC insulation flame-retardant Power Cable |
1, 2, 3, 4, 3+1, 5, 4+1, 3+2 |
1.5~630mm2 |
Operating Characteristics
Rated voltage: 0.6/1(1.2)kV
Max. permissible continuous operating temperature of conductor: 70oC
Max. temperature of conductor during short-circuit (5s max. duration) shall not exceed:
Nominal cross section of conductor ≤300mm2: 160 oC;
Nominal cross section of conductor >300mm2: 140 oC
The ambient temperature under installation should not be lower than: 0 oC
The bending radius of cable is recommended as following:
For single core cable: not less than 20 times of the diameter of cable
For multi-core cable: not less than 15 times of the diameter of cable
Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, in tunnel, in cable trench or in conduit, unable to bear external mechanical force.
Manufacturing Standards
GB/T 12706-2008, IEC 60502-1