Products


6.35/11kV CU/XLPE/PVC(or PE) Power Cable


Description
Construction: Compacted stranded circular copper conductor, extruded semi-conducting compound as conductor screen, cross-linked polyethylene(XLPE) insulation, semi-conducting compound as insulation screen, copper tape or combination of copper wire and tape as metallic screen, three cores assembled together with non-hygroscopic polypropylene filler, wrapped with binder tape, PVC or PE outer sheath.

 Type

Description

No. of cores

Nominal cross section of conductor

YJV

Copper conductor/XLPE insulation/PVC outer sheath Power Cable

1 or 3

25~800mm2

YJY

Copper conductor/XLPE insulation/PE outer sheath Power Cable

1 or 3

25~800mm2

ZA-YJV ZB-YJV ZC-YJV

Copper conductor/XLPE insulation flame-retardant Power Cable

1 or 3

25~800mm2

WDZA-YJY WDZB-YJY WDZC-YJY

Copper conductor/XLPE insulation Low Smoke Halogen Free or Zero Halogen (LSHF or LSZH) flame-retardant Power Cable

1 or 3

25~800mm2



Operating Characteristics
Rated voltage U0/U(Um): 6.35/11(12)kV
U0 is the rated power frequency voltage between conductor and earth or metallic screen for which the cable is designed;
U is the rated power frequency voltage between conductors for which the cable is designed;
Um is the maximum value of the “highest system voltage” for which the equipment may be used.
Max. permissible continuous operating temperature of conductor: 90 °C
Max. temperature of conductor during short-circuit (5s max. duration) shall not exceed: 250 °C
The ambient temperature under installation should not be lower than: 0 °C
The bending radius of cable is recommended as following:
For single core cable: not less than 20 times of the diameter of cable
For three core cable: not less than 15 times of the diameter of cable


Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, outdoors, in tunnel or in cable trench, unable to bear external mechanical force.
Single core cable in magnetic duct is not permissible.


Manufacturing Standards
GB/T 12706-2008, IEC 60502-2


ZHEJIANG KUKUN GROUP CO., LTD.
ZHEJIANG KUKUN ELECTRIC CO., LTD.
NINGBO QRUNNING CABLE CO., LTD.
CONTACT US
Email:qrunning@kukun.com
Tel:0086-574-86198928 / 86197777
Tel:0086-13505889596
Head Office Address:NO.99 Chenshan East Road, Xiaogang, Beilun, Ningbo, China